  ZGw19C SERIES - ZGw19C  
   
 
Operation Instruction
Front view
  A. Main LCD Display
  B. Power Switch
  C. Green LED Display
  D. Yellow LED Display
  E. Red LED Display
  F. Enter Button
  G. Down Button
  H. Up Button
  I. Mode Button
  J. Phone Jack
  K. Gas Entry Hole
  L. Screw Position
Back view Side view
 
 
General Introduction
 
 
Indoor Air Quality (IAQ) is measure for the quality of air in interiors, the comfortable indoor environmental quality can make people feel fresh, work efficiency and good for the health. The CO2 concentration is the important factor of good indoor air quality. People breath in oxygen and breath out CO2, nowadays people often close the windows to avoid noise and enjoy the comfort living and working environment provided by air-conditioning systems, which results in the fact that the indoor concentration of CO2 is far higher than outdoor average. With the high CO2 concentration and non- proper ventilation, people will feel headaches, dull, drowsiness, lose of concentration and correspond to the high levels of dust, chemicals and bacteria in the air.
 
 
Features & Display Features and Modes
 
 
Dual Beam NDIR (Non-Dispersive-Infrared) technology used to measure CO2
  concentration.
Three different LED display show the current Indoor Air Quality situation.
  (HVAC/ GreenHouse Mode)
Linear analog output (0~10V Voltage, 4~20mA Current) and Relay output based
  on CO2 Level.
Reliable Sensor provides long-term calibration stability.
The visual and audible alarm function can be adjustable by user.
Mounting bracket with terminal block provides quick easy installation.
 
 
LCD Display Symbol
 
 
Symbol
Meaning Description
  CO2 Concentration PPM
Parts Per Million
  The current CO2 concentration in household, greenhouse, school, hospital, exhibition, shopping mall and other office or commercial buildings.
  Alarm
  The Alarm Setting Icon, the factory setting with alarm is buzzer off.
  Calibration
  To calibrate the CO2 sensor when the accuracy deviates from the actual CO2 concentration.
  Alarm Level 1
  Under HVAC mode, Relay status will invert, the Buzzer and Yellow LED will work;
Under Greenhouse mode, Yellow LED will work.
  Alarm Level 2
  Under Greenhouse mode, Relay status will invert, the Buzzer and Green LED will work. Under HVAC mode, Red LED will work.
  Recover Factory Setting
 

To Recover Factory Setting to cancel the customized setting.

  Lock Icon
  “ON” means No key response
  BLANK
  To disable some part content of display on the LCD.
 
 
Safety Installation Step
 
 
Warning: Your safety is very important to us .To ensure you use your product correctly and safety, we would
                    like to your attention to read those warning and the User Manual before using the product. These
                    Warning provides important safety information and should be observed at all times.
1.
Please take the devices lightly, do not subject the product to impact or shock.
2.
Do not immerse the product in water.
3.
Please pay attention to the terminal block connection instruction, the wrong mode of operation or opposite
installation will destroy the circuit of the devices.
4.
Do not touch the exposed electronic circuitry of the device under any circumstances.
Keep the circuit is close during installation. As there is the danger of electric shock.
5.
Please keep the devices away from children touch to avoid the danger or the accident.
6.
Do not keep the product under the hot and moisture environment. Keep the product away form the heat
source or near water.
7.
Please ensure the screws are fixed on the wall tightly. Do not let the screws approach or close to the surface
  of PCB board during installation. It has the risk of circuit damage or irreparable damage to devices.
 
 
Caring for your product
 
 
To make sure you receive the maximum benefit from using this product, please observe the follow guideline.
1.
Cleaning --- disconnect the power before clean. Use a damp cloth; do not use the liquid cleaning agent, such
                        as benzene, thinner or aerosols.
2.
Repair --- Do not attempt to repair the product or modify the circuitry by yourself. Please contact with our local
                    dealer time or a qualified repairman if the product needs servicing.
3.
Calibration --- Please observe the calibration operation to make sure the accuracy for the devices when it’s
                            necessary.
4.
Air diffusion --- The ventilation slots on the housing are designed for CO2 diffusion, so these ventilation slots
                              should not be blocked.
 
 
Installation Step
 
 
Step 1 Step 2 Step 3
Step 4 Step 5
Step 1-3: Remove the back cover by releasing the top screw.
Step4: Secure the back cover(mounting plate) to the junction box on the wall. And make sure the wire
     connections.
Step 5: Finish the installation by mounting the controller on the back cover.
 
 
Typical Wiring Digirams
 
 
EarPhone pin define:
ZGw19 C provide earphone jack with RS232 function, How to connect please reference below picture.
 
 
Customizing Settings
 
 
 

When the power has been connected, The CO2 monitor will begin to work. In order to meet you personal requirement, it is advisable to set up the customizing parameter. Warm Up: It lasts approximately 1min before WARM UP disappears; all MODE functions will not response during warm up.

Mute Mode:

 
1.Press the MODE, the speaker icon flashes simultaneously.
2.Press ENTER, use up/down to select the on/off.
3.Press ENTER again to save the setting.

Setting the ALARM 1 level:

 
1.Press MODE, until the ALARM 1 icon flashes.
2.Press ENTER. Using the Up/Down to set the parameter. The default alarm 1 is 800 ppm (HVAC), 1000ppm (GreenHouse).
3.Press ENTER again to save the data.

Setting the ALARM 2 level:

 
1.Press MODE, until the ALARM 2 icon flashes.
2.Press ENTER. Using the Up/Down to set the parameter. The default alarm 2 is 1200ppm (HVAC), 600ppm (GreenHouse).
3.Press ENTER again to save the data.
Note: The factory setting with alarm is buzzer off; user can set the alarm on/off according to alarm function instruction.

Setting the Calibration mode:

 
1.Press the MODE. Until the CALI icon flashes.
2.Press the ENTER, CALI show on the display.
3.Adjust the display to the required CO2 value (user can pump the CO2 gas or use outside natural gas while calibrating) by up/down button.
4.Press the MODE morn than 10 sec, CALI flashes. Calibration will be done automatically after 10 minutes and LCD will display “Pass” or “Fail”. If it shows “fails”, please try again.

Setting the Alti Mode:

 
1.Press MODE, until the ALTI icon flashes.
2.Press ENTER, ALTI show on the display meter.
3.Adjust altitude by up/down button to the actual location level.
4.Press ENTER again to save the data.

Using Blank Mode:

 

1.Press MODE, until the Blank icon flashes.
2.Press ENTER, Blank show on the display of blank mode.
3. Adjust blank mode by up/down button. There are 3 kinds of mode to change.
4.Press ENTER again to save the blank statues.

Using the RcFS Mode:

 
1.Press MODE, until the RcFS flashes simultaneously.
2.Press ENTER, Using the Up/Down to select the No/Yes
3.After the slecting, Press the ENTER to save the changes.
Remark: If the user setting the data or calibrate the sensor wrongly. You can use the RcFS (Recover the factory Setting) to come back the factory setting data.
 
 
Advanced Mode
 
 
 

Press the Enter and Up together for about 10 seconds to enter Adv Mode, there will be “lock” and “mode” on the LCD. Remind these setting will change the features of LED /Relay and Analogue output.

Using Lock Icon:

 
1.Press the Enter and Up together for about 10 seconds to enter Adv Mode, there will be “Lock” on the LCD. Press Up or Down, the LCD will show “on” or “off”.
2.If select “off” and press the Enter button, these 4 keys are enable.
3.If select “on” and press the Enter button, these 4 keys are disable (will not response to the user’s action).

HVAC / Green House(GH)Mode:

 
1.Press the Enter and Up together for about 10 seconds to enter Adv Mode, Press Up or Down until appear the “mode”, then press the Enter button, the LCD will show “HVAC” or “gh”.
2.If select “HVAC” and press the Enter button, AL1 will always be less than AL2.
3.If select “gh” and press the Enter button, AL2 will always be less than AL1.
 
 
The CO2 concentration and voltage diagram
 
 
 

(The line① represents CO2 concentration, the line② represents voltage/ current)

1. When select “HVAC”, AL1 <AL2 (HVAC), if CO2 concentration is rising, the voltage/current will increase;
 
2. When select “gh”, AL1>AL2 (gh), if CO2 concentration is rising, the voltage/current will decrease.
 
Remark:
Under Green House Mode, the AL1 must >AL2.
For example: AL1= 900ppm, AL1= 800ppm now, user decrease AL1= 700ppm, AL2 will become 700-Step, (AL2= 600ppm, if step=100ppm; AL1= 680ppm, if step= 20ppm).
 
 
Specifications
 
 
  Method -Dual Beam NDIR
 

Sample Method - Diffusion or flow through (50 ~200 ml/min)

 
 
CO2 Specifications
Measurement Range
0~3,000 ppm display
Display Resolution
1ppm at 0~1,000ppm
10ppm at 1,001~3,000ppm
Accuracy ±75ppm or ±5% of reading whichever is greater
Repeatability ±20 ppm @400ppm
Temperature Dependence Typ. ±0.2% of reading per °C or ±2 ppm per °C, whichever is greater, refer­enced to 25°C
Pressure Dependence 0.13% of reading per mm Hg
Response Time About 2min for 90% of step change
Warm-Up Time About 60 seconds at 22°C
Sound Alarm About 65db@10cm
Zone LED Display

Green:<800ppm Yellow:800~1200ppm Red: >=1200ppm (HVAC mode)

Green:>1000ppm Yellow:600~1000ppm Red: <=600ppm (GreenHouse mode)
Power Supply 18~26VAC RMS 50/60Hz or 18~36VDC (half-wave rectified, polarity protected)
Linear Voltage Output 0~10VDC (100 Ohms output impedance)
Linear Current Output

4~20mA (Max Load is 500 Ohm)
( Max Load is 400 Ohm while power supply<20 VDC )

Relay Output 30VDC or 250VAC, max 2A ., SPST .Normally Open
Operating Temperature 0°C ~50°C (32°F~122°F)
Operating Humidity Range 0 ~ 95% RH non-condensing
Storage Temperature -20°C to +60°C (-4°F to 140°F)
Temperature specification
Temperature Range
Display 0°C to 50°C
Display Resolution
0.1°C
Display Options °C

Accuracy
Relay (no action and be under the alarm level)

±1°C when the fan blows to the device directly, the accuracy of temperature is +/- 1.5 °C

Accuracy
Relay (action and exceeds the alarm level)

±2.5°C when the fan blows to the device directly, the accuracy of temperature is +/- 1.5 °C
Response Time 20-30 minutes (case must equalize with environment)
RH Specification
Measurement Range
20%-90% RH
Display Resolution
1%RH
Accuracy ±5%RH@23°C

Response Time

About 5 min for 63% of step change
Operating Conditions
Operating Temperature
0°C to 50°C
Humidity Range
0 ~ 95% RH non-condensing
 
 
Dimension
 
 
 
 
Available Packages
 
 
  Dimensions: 120*120*28mm
  Weight: 210.0g
  One Set Included:
 
1 CO2 Monitor
1 White Box
 
1 User Manual    
  One Carton Included:
 
Q'ty: 30pcs
 
White Box Size: 158.5*158*48mm
 
Carton Size: 490*340*270mm;1.58 CubeFt
  N.W: 9.3kgs
  G.W: 10.1kgs